Products

Aeration Control Valves

Diamond Valve

Model-based control of aeration air.

DN 100–400 | wafer connection | air service

Diamond Valve calculates the valve opening from a flow model, with PID adjustments to support precise aeration control.

  • Intelligent multi-turn actuator with a 4–20 mA control signal.
  • 380 V / 50 Hz actuator supply in the published configuration.
  • Stainless steel valve plate with CF8 valve bodies.
  • Designed for integration into precision aeration control systems.
Download Diamond Valve brochure (PDF)

MassTrol Valve

Measure and control airflow in one valve.

DN 200–700 | flanged connection | integrated flow measurement

MassTrol combines valve positioning with airflow measurement to help address installations where the straight pipe length needed by a conventional thermal mass flowmeter is difficult to provide.

  • Accepts either a 4–20 mA valve-opening signal or a 4–20 mA airflow signal.
  • The valve HMI displays both opening position and mass flow.
  • 220 V / 50 Hz intelligent multi-turn actuator in the published configuration.
  • The centered opening supports the integrated flow measurement method.

Measurement accuracy: the brochure specifies ±1.5% with 5 pipe diameters of straight pipe upstream and 3 downstream. Confirm performance for other installation layouts with GL-TURBO.

Download MassTrol brochure (PDF)

Published specifications

Select for your air system.

These values follow the 2601 brochures. Refer to the individual drawings for dimensions and confirm the configuration for your project.

Diamond Valve and MassTrol
SpecificationDiamond ValveMassTrol
Nominal sizeDN 100–400DN 200–700
ConnectionWaferFlanged
MediumAirAir
Rated pressure (absolute)0.17 MPa0.17 MPa
Medium temperature≤150°C≤150°C
Ambient temperature−30 to 70°C−30 to 70°C
Face-to-face referenceDIN 3202/K1DIN 3202/K1
Flange referenceDIN 2532 / 1.0 MPaDIN 2532 / 1.0 MPa